Ürünler
Structure
A flame barrier mica tape is helically wrapped on the conductor made of copper wire. The cable core is formed by twisting the cores or pairs coated with LSOH insulation on the mica tape conductors, which are thick enough to meet the electrical properties. After wrapping a polyester tape with holding and protective properties on this core and a braided screen made of tinned copper wires (min. 50% coating), an orange colored LSOH sheath is covered. The outer sheath thickness shall be in accordance with TSE K 178.
Technical Information
Temperature in fixed conditions: -30 °C, +70 °C
Temperature in mobile conditions: -5 °C, +50 °C
Areas of Use
It is used as a signal and information communication cable with halogen-free and flame-retardant properties in indoor automation systems, electronic control systems, and dry environments.
Structure
The cable core is formed by twisting the cores or pairs coated with LSOH insulation, with a thickness that will meet the electrical properties, onto the conductor formed by multiple twisting of copper wires. After wrapping a polyester tape (optional) with holding and protective properties onto this core, a gray LSOH sheath is coated on it. The outer sheath thickness shall be in accordance with ÜBM-03-BK-022.
Technical Information
Temperature in fixed conditions: -30 °C, +70 °C
Temperature in mobile conditions: -5 °C, +50 °C
Areas of Use
Used as a signal and information communication cable with halogen-free and flame-retardant properties in indoor automation systems, electronic control systems, and dry environments.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
A flame barrier mica tape is helically wrapped on the conductor made of copper wire. The cable core is formed by twisting the cores or pairs coated with LSOH insulation on the mica tape conductors, which are thick enough to meet the electrical specifications. After wrapping a polyester tape (optional) with holding and protective properties on this core, an orange colored LSOH sheath is coated on it. The outer sheath thickness shall be in accordance with TSE K 178.
Technical Information
Temperature in fixed conditions: -30 °C, +70 °C
Temperature in mobile conditions: -5 °C, +50 °C
Areas of Use
It is used as a halogen-free and flame-retardant signal and information communication cable in indoor automation systems, electronic control systems, and dry environments.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
The cable core is formed by twisting PVC insulated cores or pairs with a thickness that will meet the electrical properties onto the conductor formed by multiple twisting of copper wires. After wrapping a holding and protective polyester tape (optional) onto this core, a longitudinal earth wire and 1 layer of aluminum-coated polyester tape screen with the metal part facing inward are wrapped on top to ensure the continuity of the screen. A gray PVC sheath is coated on the screen. The outer sheath thickness shall be in accordance with ÜBM-03-BK-022.
Technical Information
Temperature in fixed conditions: -30 °C, +70 °C
Temperature in mobile conditions: -5 °C, +50 °C
Areas of Use
Used as signal and information communication cable in indoor automation systems, dry environments.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
The cable core is formed by twisting the cores or pairs coated with PVC insulation, with a thickness that will meet the electrical properties, onto the conductor formed by multiple twisting of copper wires. After wrapping a polyester tape with holding and protective properties on this core and a braided screen (Min. coating 50%) consisting of tinned copper wires on it, a gray PVC sheath is covered.
The outer sheath thickness shall be in accordance with ÜBM-03-BK-022.
Technical Information
Temperature in fixed conditions: -30 °C, +70 °C
Temperature in mobile conditions: -5 °C, +50 °C
Areas of Use
It is used in indoor automation systems, electronic control systems, dry environments, as a signal and information communication cable.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
A cable core is formed by twisting the cores or pairs coated with PVC insulation in accordance with VDE 0207 Part 4 YI3, with a thickness that will meet the electrical properties, on the conductor formed by multiple twisting of copper wires.
After wrapping a polyester tape (optional) with holding and protective properties on this core, a gray sheath in accordance with VDE 0207 Part 5 YM1 is covered on it.
The outer sheath thickness shall be in accordance with ÜBM-03-BK-022
Technical Information
Temperature in fixed conditions: -30 °C, +70 °C
Temperature in mobile conditions: -5 °C, +50 °C
Areas of Use
Used in indoor automation systems, electronic control systems, dry environments, as signal and information communication cable.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Dust Cover: Aluminum, T = 1.5 (type one), T = 1.0 (type two)
Matrix: Aluminum, T = 1.5 (type one), T = 1.0 (type two)
Adapter Plate: Without
Splice Tray: Without
Panel: Aluminum
Lock: Without
Adapter: MTP (rear side), Duplex LC (front side)
Dimension: H×W×D = 34mm × 131mm × 121.5mm (type one) – H×W×D = 35mm × 141.5mm × 166.5mm (type two)
Surface Finish: Power coating
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Multi-core, fine multi-wire, copper conductor, silicone rubber insulated, flexible cables with operating temperatures of -40 ºC, +180 ºC.
Technical Information
– Manufactured in accordance with VDE 0250e.
– Minimum allowed operating temperature: -40 ºC
– Maximum allowed operating temperature: 180 ºC
– Maximum Short Circuit Temperature: 350 ºC
– Conductor Structure: Flexible
Areas of Use
They are used as internal and external flexible connection cables at continuous 180 ºC and short-term 350 ºC temperatures in dry, humid and wet locations where there is high ambient temperature and low mechanical stress.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Multi-core, single or multi-wire copper conductor, special synthetic insulation, concentric copper screen, special synthetic outer sheath, flame retardant, halogen-free, non-smoking cables during fire.
Technical Information
– Manufactured in accordance with TS HD 604 S1 5G.
– Permissible operating temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC
– Conductor Structure: Rigid
– LS (Low Smoke) Test: IEC 61034 -1/2
– Burning Droplet Test: IEC 60332-1-3
– HF (Halogen Free) Test: IEC 60754 – 1/2
– FR (Flame Resistance) Test: IEC 60332-1-2 and IEC 60332-3-24 Cat.C
– CPR (Construction Materials Directive) Test: EN 50399
Areas of Use
These cables are used in indoor and outdoor areas such as schools, hospitals, meetings and shopping malls where there are mandatory safety precautions against fire.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Multi-core, single or multi-wire copper conductor, special flame-resistant separator layer, special synthetic insulation, concentric copper conductor, special synthetic outer sheath, flame-retardant, halogen-free, non-smoking and 180 minutes flame-resistant energy and control cables according to IEC 60331-21.
Technical Information
– Manufactured in accordance with TS HD 604 S1 5G.
– Permissible operating temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC
– Conductor Structure: Rigid
– LS (Low Smoke) Test: IEC 61034 -1/2
– Burning Droplet Test: IEC 60332-1-3
– HF (Halogen Free) Test: IEC 60754 – 1/2
– FR (Flame Resistance) Test: IEC 60332-1-2 and IEC 60332-3-24 Cat.C
– FE (Current Conduction) Test: IEC 60331-21
Areas of Use
These cables are used in indoor and outdoor areas such as schools, hospitals, meetings and shopping malls where there are mandatory safety precautions against fire.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Multi-core, single or multi-wire copper conductor, special flame-resistant separator layer, special synthetic insulation, concentric copper conductor, special synthetic outer sheath, flame-retardant, halogen-free, non-smoking and 180 minutes flame-resistant energy and control cables according to IEC 60331-21.
Technical Information
– Manufactured in accordance with TS HD 604 S1 5G.
– Permissible operating temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC
– Conductor Structure: Rigid
– LS (Low Smoke) Test: IEC 61034 -1/2
– Burning Droplet Test: IEC 60332-1-3
– HF (Halogen Free) Test: IEC 60754 – 1/2
– FR (Flame Resistance) Test: IEC 60332-1-2 and IEC 60332-3-24 Cat.C
– FE (Current Conduction) Test: IEC 60331-21
Areas of Use
These cables are used in indoor and outdoor areas such as schools, hospitals, meetings and shopping malls where there are mandatory safety precautions against fire.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Single or multi-core, single or multi-wire copper conductor, special synthetic insulation, special synthetic outer sheath, flame retardant, halogen-free cables that do not create dense smoke during fire.
Technical Information
– Manufactured in accordance with TS HD 604 S1 5G.
– Permissible operating temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC
– Conductor Structure: Rigid
– LS (Low Smoke) Test: IEC 61034 -1/2
– Burning Droplet Test: IEC 60332-1-3
– HF (Halogen Free) Test: IEC 60754 – 1/2
– FR (Flame Resistance) Test: IEC 60332-1-2 and IEC 60332-3-24 Cat.C
– CPR (Construction Materials Directive) Test: EN 50399
Areas of Use
These cables are used in indoor and outdoor areas such as schools, hospitals, meetings and shopping malls where there are mandatory safety precautions against fire.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Single or multi-core, single or multi-wire copper conductor, special flame-resistant separator layer, special synthetic insulation, special synthetic outer sheath, flame-retardant, halogen-free, non-smoking and 180 minutes flame-resistant energy and control cables according to IEC 60331-21.
Technical Information
– Manufactured in accordance with TS HD 604 S1 5G.
– Permissible operating temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC
– Conductor Structure: Rigid
– LS (Low Smoke) Test: IEC 61034 -1/2
– Burning Droplet Test: IEC 60332-1-3
– HF (Halogen Free) Test: IEC 60754 – 1/2
– FR (Flame Resistance) Test: IEC 60332-1-2 and IEC 60332-3-24 Cat.C
– FE (Current Conduction) Test: IEC 60331-21
Areas of Use
These cables are used in indoor and outdoor areas such as schools, hospitals, meetings and shopping malls where there are mandatory safety precautions against fire.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Single or multi-core, single or multi-wire copper conductor, special flame-resistant separator layer, special synthetic insulation, special synthetic outer sheath, flame-retardant, halogen-free, non-smoking and 180 minutes flame-resistant energy and control cables according to IEC 60331-21.
Technical Information
– Manufactured in accordance with TS HD 604 S1 5G.
– Permissible operating temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC
– Conductor Structure: Rigid
– LS (Low Smoke) Test: IEC 61034 -1/2
– Burning Droplet Test: IEC 60332-1-3
– HF (Halogen Free) Test: IEC 60754 – 1/2
– FR (Flame Resistance) Test: IEC 60332-1-2 and IEC 60332-3-24 Cat.C
– FE (Current Conduction) Test: IEC 60331-21
Areas of Use
These cables are used in indoor and outdoor areas such as schools, hospitals, meetings and shopping malls where there are mandatory safety precautions against fire.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Single-core, single-wire, multi-wire or fine multi-wire copper conductor, special synthetic insulation, flame retardant and halogen-free energy cables.
Technical Information
– Manufactured in accordance with TS EN 50525-3-31.
– Permissible operating temperature: 70 ºC
– Maximum Short Circuit Temperature: 160 ºC
– Conductor Structure: Flexible
– LS (Low Smoke) Test: IEC 61034 -1/2
– HF (Halogen Free) Test: IEC 60754 – 1/2
– FR (Flame Resistance) Test: IEC 60332-1-2
– CPR (Construction Materials Directive) Test: EN 60332-1-2
Areas of Use
They are used as lighting and installation cables in dry spaces, switchgear facilities, distribution systems, and businesses.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file, or send it to the address you want via e-mail.
Structure
Multi-core, single or multi-wire copper conductor, special flame-resistant separator layer, special synthetic insulation, special synthetic outer sheath, flame-retardant, halogen-free, non-smoking and 180 minutes under flame function according to IEC 60331-21.
Technical Information
– Manufactured in accordance with TSE K 328.
– Permissible operating temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC
– Conductor Structure: Rigid
– LS (Low Smoke) Test: IEC 61034 -1/2
– Burning Droplet Test: IEC 60332-1-3
– HF (Halogen Free) Test: IEC 60754 – 1/2
– FR (Flame Resistance) Test: IEC 60332-1-2 and IEC 60332-3-24 Cat.C
– FE (Current Conduction) Test: IEC 60331-21
Areas of Use
They are used in facilities with a fire risk such as hotels, hospitals, shopping malls, power plants and data processing centers, and in facilities where there are many people and valuable devices where mass transportation is carried out by rail systems. These cables do not transmit flame during a fire, do not create a dense smoke layer and do not create an environment suitable for corrosion, thus ensuring the safety of life and property.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.